| Capacity |
2000VA/1800W |
| Topology |
Line Interactive, Pure Sine Wave |
| INPUT |
|
| Nominal Voltage |
240V AC |
| Acceptable Voltage Range |
162-290V AC |
| Frequency |
50/60Hz ±5Hz (auto sensing) |
| OUTPUT |
|
| Voltage Regulation (AC Mode) |
240V AC (Selectable 208/220/230V AC) ±10% AVR |
| Voltage Regulation (Batt. Mode) |
± 1.5% (before battery alarm) |
| Frequency Range (Batt. Mode) |
50Hz or 60Hz ±1Hz |
| Current Crest Ratio |
3.1 |
| Total Harmonic Distortion |
2% max @ 100% linear load, 5% max @ 100% non-linear load (before low battery alarm) |
| Transfer Time |
6ms (Typical), 10ms max. |
| Waveform (Batt. Mode) |
Pure Sine Wave |
| EFFICIENCY |
|
| AC Mode |
98% (Advanced ECO design) |
| Battery Mode |
91% |
| BATTERY |
|
| Standard Model |
Battery Type & Number: 12V/9AH (x4) Recharge Time: 4 hours recover to 90% capacity |
| PROTECTION |
|
| Full Protection |
Overload, thermal, short circuit, discharge and overcharge protection |
| Surge Protection |
1968J/39000A |
| ENVIRONMENT |
|
| Operation Temperature |
0°C~40°C |
| Relative Humidity |
0%~90% (RH non-condensing) |
| Noise Level |
<45dB |
| COMMUNICATIONS & MANAGEMENT |
|
| Interface |
USB and RS-232 as standard, an Intelligent slot for PSSNMP, PSModbus or PSAS400 dry contact |
| Software |
PowerShield NetGuard® software - supports Windows-based operating system, Linux, Unix and Mac |
| LCD display |
AC mode, Batt. Mode, Load Level, Input Voltage, Output Voltage, Overload, Fault, Battery Replacement, Low Batt., Batt. Time Remaining |
| Audible alarm |
Battery Mode, Low Battery (Batt. Mode), Battery Replacement, Fault, Overload |
| PHYSICAL |
|
| Dimensions (D x W x H) |
455 x 145 x 220mm |
| Weight |
20.5/22.5kg |
| COMPLIANCE |
|
| Safety |
EN62040-1 -1 2003, IEC 60950-1 -1 |
| EMC |
EN62040-2 2006 |
| RoHS |
Directive 2011/65/EU |